FRP cable tray support spacing is usually shorter than the spacing you would use for a steel tray of the same width and cable load. Fibreglass is strong but far less stiff than steel, so the tray reaches its deflection limit long before it reaches its breaking load. The safe span must therefore come from the manufacturer's load-span data for your actual cable load, operating temperature and tray profile, not from the support spacing used on a previous steel job.
This is the most common specification error we see when a project switches from galvanised steel to FRP or GRP for corrosion reasons. The tray material changes, but the support drawings and bracket schedule are copied across unchanged. The result is visible sag between supports, stressed splice joints and, in hot locations, deflection that keeps growing over months.
Why FRP cable tray support spacing is shorter than steel
Glass fibre reinforced plastic (FRP, also called GRP) trays are made by pultrusion or moulding, with glass fibres set in a polyester, vinyl ester or similar resin. The material has a good strength-to-weight ratio and excellent resistance to chemicals, moisture and salt air, which is why it is chosen as a corrosion resistant cable tray for chemical plants, effluent treatment areas, coastal installations and offshore-type environments.
What fibreglass does not have is steel's stiffness. Its modulus of elasticity is a fraction of steel's, and deflection under load is inversely proportional to that stiffness. For the same section shape, span and load, an FRP tray bends noticeably more than a steel one. Manufacturers compensate with deeper side rails and thicker profiles, but in practice the support span is the main tool for controlling sag.
Steel trays, by comparison, are normally limited by strength and connection capacity before deflection becomes the deciding factor. If you are used to specifying GI and hot dip galvanised cable trays, expect FRP spans for an equivalent load to be tighter, and check every run rather than applying one blanket spacing across the project.
Deflection, creep and temperature: what governs the span
Three effects decide how far an FRP tray can safely span between supports.
Short-term deflection
This is the immediate sag when cables are laid. Published standards for fibreglass trays address it directly: NEMA FG 1, the NEMA standard for fibreglass cable tray systems, sets out load classes and the test method for rating trays by working load over a stated span. IEC 61537, the international standard for cable tray and cable ladder systems, likewise defines safe working load through testing with limits on deflection. When you compare FRP trays from different suppliers, ask which test basis their load-span table follows.
Creep under sustained load
Cables sit on a tray for decades. Under constant load, resin-based composites slowly continue to deflect, an effect known as creep. Steel does not behave this way at normal ambient temperatures. A span that looks acceptable on the day of installation can sag further over time if it was selected at the edge of the short-term table.
Operating temperature
The stiffness and strength of FRP reduce as temperature rises. Rooftop runs in Pune's summer, trays near furnaces or process lines, and pipe racks exposed to direct sun in Mumbai or the Gulf all run hotter than ambient. Load-span data is normally given at a reference temperature, and manufacturers apply a derating at higher temperatures. Always state the maximum expected surface temperature in your enquiry, not just the design ambient.
What changes the safe span on your project
Selecting the right cable tray depends on cable load, installation environment, support spacing, material and required finish. For FRP, review these points run by run:
- Cable load per metre: calculate it from the cable schedule, including the weight of armoured power cables, and add an allowance for future cables.
- Tray type and profile: ladder and perforated FRP trays behave differently, and side rail height has a large effect on stiffness.
- Tray width: wider trays carry more cable, so the load per metre rises even if the span does not change.
- Concentrated loads: people standing on trays during installation, junction boxes or heavy single cores laid in one bunch create point loads that uniform-load tables do not cover.
- Environment: temperature, UV exposure, wind on outdoor runs and any ice or dust build-up.
- Continuous or simple span: a tray running continuously over several supports deflects less than a single isolated span.
For heavy HT cable runs where long spans are unavoidable, our article on supporting heavy power cables in long-span installations explains the options, including intermediate supports and deeper sections.
Supports, splices and fixings for FRP cable tray systems

Getting the span right is only half the job. The support system has to match the reason you chose FRP in the first place.
- Splice location: common installation practice, reflected in guidance such as NEMA VE 2 on cable tray installation, is to keep splice joints close to supports (around the quarter-span point) rather than at mid-span, where bending moment and deflection are highest. This matters even more with FRP.
- Support material: installing FRP trays on plain mild steel brackets in a chemical or coastal area simply moves the corrosion problem to the supports. Use FRP supports, stainless steel (SS 304 or SS 316, depending on the environment) or suitably finished steel matched to the site conditions.
- Fasteners: specify FRP or stainless steel bolts and nuts. Mixed metals in a wet, corrosive area can lead to galvanic corrosion at the fixing.
- Cut edges: any tray cut at site should have its edges sealed with a compatible resin so the glass fibres are not exposed to moisture and chemicals.
- Hold-down and expansion: allow for thermal movement on long outdoor runs and use clamps that guide the tray rather than lock it rigidly at every support.
To see how the wrong support material shortens system life, read how corrosion impacts cable tray lifespan.
How to specify FRP cable tray support spacing in your tender
A clear specification avoids site arguments later. We recommend including the following in your technical specifications or BOQ notes:
- Tray type (ladder, perforated or solid), width, side rail height and resin system.
- Design cable load in kg per metre, with the future allowance stated.
- Maximum support spacing for each tray size, taken from the manufacturer's load-span data.
- Deflection limit and the standard or test basis used to rate the tray, such as NEMA FG 1 or IEC 61537.
- Maximum operating temperature and whether the run is exposed to direct sunlight.
- Fire performance and UV requirements for the resin.
- Support, splice plate and fastener material.
If your project is still deciding between FRP, stainless steel, hot dip galvanised to IS-2629 or pre-galvanised to IS-277 finishes, our page on cable tray materials and finishing compares the options and where each one fits.
Working with an FRP cable tray manufacturer on span data

An experienced FRP cable tray manufacturer should do more than send a price per metre. Before you finalise support drawings, share your cable schedule, routing layout and site conditions, and ask for span recommendations for each tray size. Where the standard profile needs very close supports, a deeper side rail or a different tray width can often reduce the total number of brackets, which saves installation cost across a large project.
Hutaib Electricals has manufactured cable trays and cable tray accessories and fittings in Pune since 2001, with in-house manufacturing, quality control and packing. We supply industrial cable management systems to EPC contractors, MEP consultants and procurement teams across Maharashtra, pan India and export markets including the UAE, Nepal, Bangladesh and Bhutan. Our full range of FRP and GRP cable trays covers corrosive, coastal and chemical environments, with custom made cable trays for project-specific requirements.
For bulk cable tray requirements or a span review, share your drawings, cable schedule, operating temperature and required quantities with our team and request a quotation. We will confirm tray profile, recommended support spacing and fittings before you commit to the support layout.
Frequently asked questions
Can I use the same support spacing for FRP trays as for GI steel trays?
Usually not. FRP is much less stiff than steel, so for the same width and cable load it deflects more and generally needs closer supports. Take the spacing from the FRP manufacturer's load-span data for your actual load and temperature.
Does high temperature affect FRP cable tray support spacing?
Yes. FRP loses stiffness and strength as temperature rises, so trays on rooftops, near process heat or in direct sun need a temperature derating. State the maximum expected tray surface temperature when you request span recommendations.
Where should splice joints be placed on an FRP cable tray run?
Keep splices close to supports, around the quarter-span point, rather than at mid-span where bending and deflection are greatest. This is common installation practice for cable trays and is especially important for fibreglass.
What supports and fasteners should be used with FRP cable trays?
Use FRP supports or stainless steel (SS 304 or SS 316 depending on the environment), with FRP or stainless steel fasteners. Plain mild steel brackets in a corrosive area will corrode and undo the benefit of choosing FRP.
What information do you need to recommend spans and quote for FRP trays?
Share the cable schedule or load per metre, tray routing drawings, tray sizes, operating temperature, indoor or outdoor exposure and required quantities. With this, Hutaib Electricals can confirm a suitable tray profile, support spacing and fittings along with the quotation.